The Transmission Company of Nigeria (TCN), has said that at about 6:10pm on Monday, 5th August 2024, power supply was restored to areas that had been affected by the arcing on the Benin-Egbin 330kV isolator which caused lines tripping and consequent loss of supply to some areas.
However, contrary to reports, the incident did not cause a system collapse.
According to the company, the line tripping started earlier at about 2:47 p.m. yesterday, with a heavy system surge that led to the arcing of Benin – Egbin 330kV line isolator fingers at the Egbin Transmission Substation switchyard.
This resulted in a tripping at the Egbin Generating Station, which caused the loss of power supply to all the Egbin Transmission Substations’ outgoing lines. This led to an exponential increase in load on the Osogbo-Ihovbor 330kV line 1 with serious arcing of isolator terminals on the Osogbo-Ihovbor 330kV line 1. To ensure that the sequence of events does not affect the nation’s grid, the Osogbo – Ihovbor 330kV line was opened to temporarily cut off the flow of electricity on that line.
ALSO READS:
- LASTMA Rescues 17 as CNG-Powered Bus Goes Up in Flames in Lagos
- Nigeria’s Oil Sector Rig Count Hits 100
- Power restored to Lagos, Ogun, four other locations after vandalism – Minister
- NNPC Confirms Gas Availability, Says No Constraints on Deliveries to Power Plants
- Gas Shortage, Low Water Levels Trigger Decline in Nigeria’s Power Generation — NISO
“At about 2:56pm, however, the Benin-Egbin 330kV line 1 Circuit Breaker also tripped at the Benin Transmission Substation end and this resulted in the loss of supply to Lagos axis, parts of the South West Region, parts of the North Central and Abuja. Meanwhile, other areas, including the South Eastern region, North East, and other parts of North Central and South West, had full power supply.”

“The line tripping was quickly rectified, enabling the grid controller to restore full bulk power supply through the transmission lines at about 6.10pm yesterday”, it stated in a statement.